Effective
2/97 Page i
INTRODUCTION
GENERAL
This service manual has four chapters covering the MRC-400/450 Mobile Recycling Center, and
MTC-4000/4500. The serial A units will be refereed to as MRC-400/450. The manual covers the following topics:
AC/DC Distribution, Theory of Operation / Troubleshooting, Maintenance and Calibration Procedures, and a Parts
List.
The MRC-400/450, and MTC-4000/4500 are capable of the following functions:
1. Reclaim, clean, and store refrigerant for reuse.
2. Pull a vacuum on an Air Conditioning System.
3. Accurately charge an Air Conditioning System with refrigerant.
4. MRC-400/MTC-4000: Charges R-12, and R-500.
5. MRC-450/MTC-4500: Charges R-134a.
NOTE: The following is a breakdown description for Serial Numbers:
Serial # Location - Rear Cabinet top right hand side.
Example: 0692A0101
06 Month MFG.
92 Year MFG.
A Serial Rev.
0101 Number of Unit.
NOTE: MRC-400/450 WITH A DATE CODE OF XX92 AND EARLY XX93 MAY HAVE THE LETTERS A, B,
OR C. THESE ARE SERIAL A UNITS. PLEASE CONFIRM BY CHECKING SOFTWARE LEVEL,
SEE BELOW.
SERIAL A SOFTWARE STARTS WITH 1.XX ON POWER UP.
FUNCTIONAL DESCRIPTION
Auto Sequence: Press <AUTO SEQUENCE> to begin an automatic sequence: Recovery, Evacuate, Vacuum
Hold, Oil Charge and Refrigerant Recharge. The unit can automatically recall entries from the last AUTO
SEQUENCE operation by pressing and holding the <AUTO SEQUENCE> for five seconds.
Reclaim Only: Press <RECLAIM ONLY> to recover refrigerant from the air conditioning system. Refrigerant
gas enters the MRC-400's suction separator through two service hoses. The unit traps oil and solid contaminants
at the bottom of the separator bowl. The pump pulls refrigerant gas from the top of the bowl. Then the
compressor compresses the refrigerant to a high-pressure gas.
Next, the high-pressure refrigerant gas enters the condenser. Two continuously running fans blow air across the
condenser. The air removes heat and condenses the high-pressure gas into a high-pressure refrigerant liquid.
The liquid flows out of the Condenser and through the Master Filter/Drier. The unit collects the refrigerant in the
recovery tank. When the unit finishes reclaiming, the operator panel is green, COMPLETED LED lights. Unit can
display the amount of refrigerant recovered that was added to the scale by pressing the <AMOUNT>.
Seitenansicht 0
1 2 3 4 5 6 ... 152 153

Inhaltsverzeichnis

Seite 1 - INTRODUCTION

Effective2/97 Page iINTRODUCTIONGENERALThis service manual has four chapters covering the MRC-400/450 Mobile Recycling Center, andMTC-4000/4500. The

Seite 2 - ELECTRONIC SAFETY PRECAUTIONS

CHAPTER 1 AC/DC POWER DISTRIBUTION (A)EffectivePage 1-2 2/97DC DISTRIBUTIONPROCESSOR BOARDThe Processor Board has three bridge rectifiers and one 5 vo

Seite 3 - SERVICE GUIDELINES

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-10 2/97RECOVERED CHARGE MODEIn this cycle the Zero “0” solenoid is CLOSED and the Reclaim solenoids

Seite 4 - INTRODUCTION (A)

CHAPTER 2 THEORY OF OPERATION (B)Effective2/97 Page 2-11VIRGIN CHARGE MODEIn this cycle the Liquid solenoid is CLOSED and the Virgin and Crossover so

Seite 5 - CHAPTER 2 THEORY OF OPERATION

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-12 2/97SUCTION SEPARATOR MODEThe Suction Separator cycle can be activated either by the Suction Sepa

Seite 6 - APPENDIX B ERROR CODES

CHAPTER 2 THEORY OF OPERATION (B)Effective2/97 Page 2-13TROUBLESHOOTINGCOMPLAINT CORRECTIVE ACTIONI. Error Code 0.Internal CPU memory failure.Check f

Seite 7 - APPENDIX E SOFTWARE FLOW

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-14 2/97COMPLAINT CORRECTIVE ACTIONVIII. Error Code 7.No weight drop fromscaleduring refrigerantchar

Seite 8

CHAPTER 2 THEORY OF OPERATION (B)Effective12/98 Page 2-15COMPLAINT CORRECTIVE ACTIONXIII. Error Code 12.Tank Full and Tank Emptylights are on at th

Seite 9

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-16 12/98COMPLAINT CORRECTIVE ACTIONXIX. Error Code 18.Present Purge pressure isgreater than 500 PSI

Seite 10 - DC DISTRIBUTION

CHAPTER 2 THEORY OF OPERATION (B)Effective12/98 Page 2-17COMPLAINT CORRECTIVE ACTIONXXIII. Error Code 22.Vacuum loss greater than2"HG in Hold.•

Seite 11 - CHECK OUT PROCEDURE

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-18 12/98COMPLAINT CORRECTIVE ACTIONXXX. Error Code 29.No refrigerant tankscharging.• Install a R-1

Seite 12

SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0695 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All information contained or d

Seite 13 - 1-1 1-5/6

CHAPTER 1 AC/DC POWER DISTRIBUTION (A)Effective2/97 Page 1-3ALARMThe alarm is powered by the 24 volt DC voltage at J1 pin1. A beeper driver is used t

Seite 14 - THEORY OF OPERATION

Effective2/97 Page 3-1CHAPTER 3CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURESCHECKOUT PROCEDURES!USE STANDARD REFRIGERANT HANDLINGSAFETY PROCEDURES WHEN

Seite 15 - RECLAIM LOW, HIGH MODES

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)EffectivePage 3-2 2/97CHECKOUT CHARGE AND RECLAIM PLUMBINGClose both hand valves at the end o

Seite 16 - RECLAIM LOW, HIGH MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)Effective12/98 Page 3-3R134a VEHICLE ADAPTERS CHECKOUT PROCEDURETOOLS REQUIRED: R134a Service

Seite 17 - FIGURE 2-3 RECOVERY HOLD MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)EffectivePage 3-4 12/98FLOW TEST DIAGNOSTICS (ELECTRIC)PREREQUISITES: Both tanks must have r

Seite 18 - FIGURE 2-4 OIL RETURN MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)Effective12/98 Page 3-5 FLOW TEST DIAGNOSTIC continued...18. Suction Separator solenoid is op

Seite 19 - PURGE MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)EffectivePage 3-6 12/98TRANSDUCER CALIBRATIONNOTE: UNIT CAN NOT ENTER CALIBRATION IF TRANSDUC

Seite 20 - FIGURE 2-6 VACUUM MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)Effective12/98 Page 3-7PROCEDURE FOR CHANGING OIL / OIL SHOULD BE CHANGED EVERY 90 DAYSOIL RE

Seite 21 - FIGURE 2-7 OIL CHARGE MODE

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)EffectivePage 3-8 12/98PUMP MAINTENANCECHANGING OIL USING A VACUUM SOURCE TO DRAW OUT THE OIL

Seite 22

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)Effective12/98 Page 3-9Removing oil without catheter tube:1. If there is any refrigerant or

Seite 23

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (B)EffectivePage 3-10 12/98PROCEDURE TO DISASSEMBLE BLOCK ASSEMBLYCAUTION:ALWAYS WEAR GOGGLES AN

Seite 24

CHAPTER 1 AC/DC POWER DISTRIBUTION (A)EffectivePage 1-4 2/97TROUBLESHOOTINGCOMPLAINT CORRECTIVE ACTIONI. Machine will not power up.Is the machine plug

Seite 25

Effective12/98 Page 4-1CHAPTER 4PARTS_______________________________________________________________________________________PARTS BY PICTORIALThis cha

Seite 26

CHAPTER 4 PARTS (B)Effective12/98 Page 4-2FRONT VIEWITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Headsign, Sun Decal 0682-0964-01 7. La

Seite 27

CHAPTER 4 PARTS (B)Effective12/98 Page 4-3REAR VIEWITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Label, "Caution Vent" 0682-10

Seite 28

CHAPTER 4 PARTS (B)Effective12/98 Page 4-4TOP VIEW OF PUMP COMPARTMENTITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Condenser 0111-0703-

Seite 29

CHAPTER 4 PARTS (B)Effective12/98 Page 4-5TOP OF HEADFRAMEITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1a. Power Supply (110V.A.C.) 7009-2

Seite 30

CHAPTER 4 PARTS (B)Effective12/98 Page 4-6MANIFOLD BLOCK ASSEMBLYITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Manifold 7009-2393-06 6.

Seite 31 - Page 2-18 12/98

CHAPTER 4 PARTS (B)Effective12/98 Page 4-7HOSE PART NUMBERSITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBERT1 Tube (Aluminum) 7009-2427-01 H8

Seite 32 - 2-1 2-17/18

CHAPTER 4 PARTS (B)Effective12/98 Page 4-8ADAPTERS / FITTINGSGM ADAPTER FORD ADAPTER0647-0196-01 0647-0200-01LARGE GM ADAPTER QUICK DISCONNECT GM/FORD

Seite 33

CHAPTER 4 PARTS (B)Effective12/98 Page 4-9SUCTION SEPARATOR VIEWITEM DESCRIPTION EQUI SERV #1. Cap and shield 7020-1982-012. Fitting, nipple 4982-0074

Seite 34

CHAPTER 4 PARTS (B)Effective12/98 Page 4-10PARTS IN ALPHABETICAL ORDERNAME PART NUMBER 40041004504500COMMENTSAdapter, FORD 0647-0200-01 X Standard Scr

Seite 35 - CHECKOUT COMPLETE

SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0695 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All information contained or d

Seite 36

CHAPTER 4 PARTS (B)Effective12/98 Page 4-11NAMEPART NUMBER 40041004504500COMMENTSFitting, Tubo 0647-0206-01 X XFitting, nipple 4982-0073-01 X X In S.

Seite 37

CHAPTER 4 PARTS (B)Effective12/98 Page 4-12NAMEPART NUMBER 40041004504500COMMENTSO-Ring 0617-0211-06 X X Between the front 2 blocksO-Ring 0617-0211-07

Seite 38 - TRANSDUCER CALIBRATION

CHAPTER 4 PARTS (B)Effective12/98 Page 4-13PARTS IN NUMERICAL ORDERNAME PART NUMBER 40041004504500COMMENTSWrench, Filter 0001-0067-01 X XCondenser 011

Seite 39

CHAPTER 4 PARTS (B)Effective12/98 Page 4-14NAMEPART NUMBER 40041004504500COMMENTSScrew, Thumb 0675-0157 X X Oil BracketCompressor Oil 0681-0179-02 X X

Seite 40

CHAPTER 4 PARTS (B)Effective12/98 Page 4-15NAMEPART NUMBER 40041004504500COMMENTSPlate 4982-0076-01 X X In S. S. bowlValve, Hand 5121-0004-01 XLatch 5

Seite 41 - COMPLETE

CHAPTER 4 PARTS (B)Effective12/98 Page 4-16

Seite 42

SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0895 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All information contained or d

Seite 43

CHAPTER 4 PARTS (B)

Seite 44 - TO OPERATE PROPERLY

Effective12/98 Page A-1APPENDIX ACONFIGURATIONMRC-400/ATC-4100 REFRIGERANT TYPEI. USE OF R-12 on Serial “B”II. USE OF R-500 on Serial “B”III. USE OF R

Seite 45 - TOP VIEW OF PUMP COMPARTMENT

APPENDIX A CONFIGURATION (B)EffectivePage A-2 12/98

Seite 46 - TOP OF HEADFRAME

Effective12/98 Page 2-1CHAPTER 2THEORY OF OPERATION OPERATING MODES FOR SERIAL "A"POWER ON MODEThe Power On Mode is activated by turning on

Seite 47 - CHAPTER 4 PARTS (A)

APPENDIX A CONFIGURATION (B)Effective2/97 Page A-3BOARD CONFIGURATIONSPROCESSOR BOARD 7001-2188-021 8J4 1 6J71 8 1 6J5J31211121 7J2 J81 7 11 44 J1J681

Seite 48

APPENDIX A CONFIGURATION (B)EffectivePage A-4 2/97LEFT LCD DISPLAY BOARD 7001-2153-01RIGHT LCD DISPLAY BOARD 7001-2153-01

Seite 49

Effective2/97 Page B-1APPENDIX BERROR CODESThe Refrigerant Recovery System has a self-diagnostic feature. When a malfunction with the Recovery System

Seite 50

APPENDIX B ERROR CODES (B)EffectivePage B-2 2/97ERROR CODES 14 THROUGH 26ERROR CODE DESCRIPTION POSSIBLE CAUSE14Discharge pressure greater than 500 ps

Seite 51

APPENDIX B ERROR CODES (B)Effective2/97 Page B-3ERROR CODES 27 THROUGH 30ERROR CODE DESCRIPTION POSSIBLE CAUSE27Incorrect refrigerant settings.• Refer

Seite 52

APPENDIX B ERROR CODES (B)EffectivePage B-4 2/97

Seite 53

Effective2/97 Page C-1APPENDIX CSOFTWARE/HARDWARE REVISIONThis appendix will give a breakdown of each software revision. The first section list the r

Seite 54

APPENDIX C SOFTWARE/HARDWARE REVISION (B)EffectivePage C-2 2/97REVISION 2.05 continue...∗ Added one extra count to charge target weight to compensate

Seite 55

APPENDIX C SOFTWARE/HARDWARE REVISION (B)Effective2/97 Page C-3REVISION 2.20∗ Not to be used. All future versions will only support new small oil sep

Seite 56

APPENDIX C SOFTWARE/HARDWARE REVISION (B)EffectivePage C-4 2/97HARDWARE REVISIONSLCD BOARD 7001-2153-01REVISION A: (11-12-91); NEW RELEASE.REVISION B:

Seite 57

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-2 12/98AUTO SEQUENCE MODEIn this Mode the MRC-400/450 will automatically recover the system, recycle

Seite 58

APPENDIX C SOFTWARE/HARDWARE REVISION (B)Effective2/97 Page C-5REVISION CONTROLMINIMUM REWORK MINIMUM REVISION CURRENT REVISION7001-2153-01A B B7001-2

Seite 59

APPENDIX C SOFTWARE/HARDWARE REVISION (B)EffectivePage C-6 2/97

Seite 60

Effective2/97 Page D-1APPENDIX DINSTALLATION INSTRUCTIONSAppendix D is reserved for filing of Installation Instructions. When a kit is successfully i

Seite 61

APPENDIX D INSTALLATION INSTRUCTIONSEffectivePage D-2 2/97

Seite 62

CHAPTER 2 THEORY OF OPERATION (A)Effective12/98 Page 2-3RECLAIM LOW, HIGH MODES continue...RECLAIMTANKVAPORLIQUIDVIRGINTANKOILBOTTLESCALEINPURGETRANSD

Seite 63

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-4 12/98RECLAIM HOLD MODEIn Reclaim Hold, only the Purge solenoid is ON, allowing the Purge Transducer

Seite 64 - APPENDIX A CONFIGURATION (A)

CHAPTER 2 THEORY OF OPERATION (A)Effective2/97 Page 2-5OIL RETURN MODEAs the compressor functions, small amounts of oil is carried off with the compre

Seite 65

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-6 2/97PURGE MODEThe purpose of the Purge cycle is to remove non-condensables (Air) from the Recovery

Seite 66 - Page A-4 8/95

INTRODUCTION (A)EffectivePage ii 2/97FUNCTIONAL DESCRIPTION continue...Vacuum: After you open a vehicle air conditioning system, you cannot immediate

Seite 67

CHAPTER 2 THEORY OF OPERATION (A)Effective2/97 Page 2-7VACUUM MODEDuring this cycle the Vacuum, Crossover, Suction Separator, Purge and Zero solenoids

Seite 68 - ERROR CODES 13 THROUGH 24

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-8 2/97VACUUM HOLD MODENO FIGURE SHOWN: After the Vacuum cycle, the MRC-400/450 will hold a vacuum fo

Seite 69 - ERROR CODES 25 THROUGH 30

CHAPTER 2 THEORY OF OPERATION (A)Effective2/97 Page 2-9RECOVERED CHARGE MODEIn this cycle the Liquid solenoid is CLOSED and the Reclaim and Crossover

Seite 70

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-10 2/97VIRGIN CHARGE MODEIn this cycle the Liquid solenoid is CLOSED and the Virgin and Crossover sol

Seite 71

CHAPTER 2 THEORY OF OPERATION (A)Effective2/97 Page 2-11SUCTION SEPARATOR MODEThe Suction Separator cycle can be activated either by the Suction Separ

Seite 72

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-12 2/97TROUBLESHOOTINGCOMPLAINT CORRECTIVE ACTIONI. Error Code 0.Internal CPU memory failure.Check fo

Seite 73

CHAPTER 2 THEORY OF OPERATION (A)Effective2/97 Page 2-13COMPLAINT CORRECTIVE ACTIONVIII. Error Code 7.No weight drop fromscaleduring refrigerantcharg

Seite 74

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-14 2/97COMPLAINT CORRECTIVE ACTIONXIII. Error Code 12.Tank Full and Tank Emptylights are on at the s

Seite 75

CHAPTER 2 THEORY OF OPERATION (A)Effective12/98 Page 2-15COMPLAINT CORRECTIVE ACTIONXIX. Error Code 18.Present Purge pressure isgreater than 500 PSI.

Seite 76

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-16 12/98COMPLAINT CORRECTIVE ACTIONXXIII. Error Code 22.Vacuum loss greater than 2"HG in Hold.•

Seite 77

INTRODUCTION (A)Effective2/97 Page iiiREFRIGERANT SAFETY WARNINGS!USE STANDARD REFRIGERANT HANDLINGSAFETY PROCEDURES WHEN PERFORMING INSTALLATIONALWAY

Seite 78

CHAPTER 2 THEORY OF OPERATION (A)Effective12/98 Page 2-17COMPLAINT CORRECTIVE ACTIONXXX. Error Code 29.No refrigerant tankscharging.• Install a R-12

Seite 79

CHAPTER 2 THEORY OF OPERATION (A)EffectivePage 2-18 12/98

Seite 80 - INTRODUCTION (B)

SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0695 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All information contained or d

Seite 81 - 2/97 Page v

Effective2/97 Page 3-1CHAPTER 3CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURESCHECKOUT PROCEDURES!USE STANDARD REFRIGERANT HANDLINGSAFETY PROCEDURES WHEN

Seite 82

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)EffectivePage 3-2 2/97CHECKOUT CHARGE AND RECLAIM PLUMBING1. Close both hand valves at the en

Seite 83

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)Effective2/97 Page 3-3R134a VEHICLE ADAPTERS CHECKOUT PROCEDURETOOLS REQUIRED: R134a Service

Seite 84

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)EffectivePage 3-4 2/97FLOW TEST DIAGNOSTICS (ELECTRIC)PREREQUISITES:Flow test (Displayed: &qu

Seite 85

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)Effective2/97 Page 3-5FLOW TEST DIAGNOSTIC continued...17. Vacuumed solenoid S6 is opened. L

Seite 86 - AC/DC POWER DISTRIBUTION

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)EffectivePage 3-6 2/97RECLAIM TANK PROCEDURE FOR ADJUSTING ZERO W/REFRIGERANT IN TANKTOOLS RE

Seite 87

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)Effective2/97 Page 3-7MAINTENANCE PROCEDURESTEMPRITE/OIL RESERVOIR CHECKOUT PROCEDURETools Re

Seite 88

INTRODUCTION (A)EffectivePage iv 2/97HANDLING MOS IC'S AND THEIR STATIC SENSITIVE DEVICESMost integrated circuits are high impedance devices. Th

Seite 89

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)EffectivePage 3-8 2/97 OIL RESERVOIR MAINTENANCE continue...12. Carefully reinstall the oil r

Seite 90

CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURES (A)Effective2/97 Page 3-9PROCEDURE TO DISASSEMBLE BLOCK ASSEMBLYCAUTION: ALWAYS WEAR GOGGLES AND

Seite 91

Effective12/98 Page 4-1CHAPTER 4PARTS_______________________________________________________________________________________PARTS BY PICTORIALThis cha

Seite 92

CHAPTER 4 PARTS (A)EffectivePage 4-2 12/98FRONT VIEWITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1a. Headsign, Sun Decal 0682-0964-01 6. S

Seite 93 - RECOVER LOW, HIGH MODE

CHAPTER 4 PARTS (A)Effective12/98 Page 4-3REAR VIEWITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Label, "Caution Vent" 0682-1

Seite 94 - RECOVERY HOLD MODE

CHAPTER 4 PARTS (A)EffectivePage 4-4 12/98TOP VIEW OF PUMP COMPARTMENTINOUT356891112413b1417161513a71210MT1MT2MT3LP TRANSPRGTRANSHPCOHPTRANSLPCOROTATI

Seite 95

CHAPTER 4 PARTS (A)Effective12/98 Page 4-5TOP OF HEADFRAME132a678910611122c2bTOP VIEWUNDER CONTROL PANELMRC/MTC CONTROL PANEL1312345677076-0897-017076

Seite 96 - FIGURE 2-5 PURGE MODE

CHAPTER 4 PARTS (A)EffectivePage 4-6 12/98MANIFOLD BLOCK ASSEMBLYITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBER1. Manifold Assembly 7009-23

Seite 97

CHAPTER 4 PARTS (A)Effective12/98 Page 4-7HOSE PART NUMBERSITEM DESCRIPTION PART NUMBER ITEM DESCRIPTION PART NUMBERH1. Red 16" 3988-0265-01 H16.

Seite 98

CHAPTER 4 PARTS (A)EffectivePage 4-8 12/98ADAPTERS / FITTINGSGM ADAPTER FORD ADAPTER0647-0196-01 0647-0200-01LARGE GM ADAPTER QUICK DISCONNECT GM/FORD

Seite 99

TABLE OF CONTENTS FOR SERIAL AEffective2/97INTRODUCTIONGENERAL...

Seite 100 - RECOVERED CHARGE MODE

CHAPTER 4 PARTS (A)Effective12/98 Page 4-9SUCTION SEPARATORITEM DESCRIPTION EQUI SERV #1. Cap and shield 7020-1982-012. Fitting, nipple 4982-0074-013.

Seite 101 - FIGURE 2-9 VIRGIN CHARGE MODE

CHAPTER 4 PARTS (A)EffectivePage 4-10 12/98PARTS IN ALPHABETICAL ORDERNAME PART NUMBER 400 450 COMMENTSAdapter, Ford 0647-0200-01 XAdapter, GM 0647-01

Seite 102 - BACKGROUND RECLAIM MODE

CHAPTER 4 PARTS (A)Effective12/98 Page 4-11NAMEPART NUMBER 400 450 COMMENTSFitting 0647-0223-01 X X 1/4” FlareFitting, Atomizer 7024-0511-01 X XFittin

Seite 103 - TROUBLESHOOTING

CHAPTER 4 PARTS (A)EffectivePage 4-12 12/98NAMEPART NUMBER 400 450 COMMENTSMoisture Indicator 7009-2346-01 X XNipple, Hex 4982-0076-01 X XO-Ring 0617-

Seite 104 - COMPLAINT CORRECTIVE ACTION

CHAPTER 4 PARTS (A)Effective12/98 Page 4-13NAMEPART NUMBER 400 450 COMMENTSVaristor 7009-1320 X X (115 V)Varistor 7009-1320-02 X X (220 V)Vent tube to

Seite 105

CHAPTER 4 PARTS (A)EffectivePage 4-14 12/98PARTS IN NUMERICAL ORDERNAME PART NUMBER 400 450 COMMENTSCondenser 0111-0703-01 X XOil Separator, Small 011

Seite 106

CHAPTER 4 PARTS (A)Effective12/98 Page 4-15NAMEPART NUMBER 400 450 COMMENTSDesiccant Bags 0671-1018-01 X (Qty. 10)Desiccant Bags 0671-1018-02 X (Qty.

Seite 107

CHAPTER 4 PARTS (A)EffectivePage 4-16 12/98NAMEPART NUMBER 400 450 COMMENTSGasket 4053-0020-01 X X Suction Separator BowlConnector, CPC 4 Pin 4162-083

Seite 108

CHAPTER 4 PARTS (A)Effective12/98 Page 4-17GRAPHICS KITS P/N'S FOR GENERIC UNITS IN BRAND NAME ORDER:NOTE: 1091 KITS ARE IN FINISHED GOODS STOCK

Seite 109 - 2-1 2-19/20

CHAPTER 4 PARTS (A)EffectivePage 4-18 12/98

Seite 110 - CHAPTER 3

TABLE OF CONTENTS FOR SERIAL AEffective2/97CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURESCHECKOUT PROCEDURES ...

Seite 111

CHAPTER 4 PARTS (A)SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0895 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All informa

Seite 112

CHAPTER 4 PARTS (A)

Seite 113

CHAPTER 4 PARTS (A)

Seite 114 - PRESSURE

Effective12/98 Page A-1APPENDIX ACONFIGURATIONMRC-400/MTC-4000 REFRIGERANT TYPEI. USE OF R-12II. USE OF R-500III. USE OF R-134aONOFFREFRIGERANT TYPE S

Seite 115 - MAINTENANCE PROCEDURES

APPENDIX A CONFIGURATION (A)EffectivePage A-2 12/98

Seite 116 - CALIBRATION COMPLETE

APPENDIX A CONFIGURATION (A)Effective8/95 Page A-3BOARD CONFIGURATIONSPROCESSOR BOARD 7001-2188-011 8J4 1 6J71 8 1 6J5J31211121 7J2 J81 7 11 44 J1J681

Seite 117 - PUMP MAINTENANCE

APPENDIX A CONFIGURATION (A)EffectivePage A-4 8/95LEFT LCD DISPLAY BOARD 7001-2153-01RIGHT LCD DISPLAY BOARD 7001-2153-01

Seite 118 - Figure - 1

Effective2/97 Page B-1APPENDIX BERROR CODESThe Refrigerant Recovery System has a self-diagnostic feature. When a malfunction with the Recovery System

Seite 119

APPENDIX B ERROR CODES (A)EffectivePage B-2 2/97ERROR CODES 13 THROUGH 24ERROR CODE DESCRIPTION POSSIBLE CAUSE13Discharge pressure less than 30” HG.•

Seite 120 - CHAPTER 4

APPENDIX B ERROR CODES (A)Effective2/97 Page B-3ERROR CODES 25 THROUGH 30ERROR CODE DESCRIPTION POSSIBLE CAUSE25Discharge Temperature less than 20°F.

Seite 121 - FRONT VIEW

TABLE OF CONTENTS FOR SERIAL AEffective2/97REVISION CONTROL...

Seite 122 - CHAPTER 4 PARTS (B)

APPENDIX B ERROR CODES (A)EffectivePage B-4 2/97

Seite 123

Effective2/97 Page C-1APPENDIX CSOFTWARE/HARDWARE REVISIONThis appendix will give a breakdown of each software revision. The first section list the r

Seite 124 - DISCHARGE PRESSURE

APPENDIX C SOFTWARE/HARDWARE REVISION (A)EffectivePage C-2 2/97REVISION 1.14∗ NOT RELEASED TO PRODUCTION∗ Fixed bug when cancelling out of vacuum hold

Seite 125 - Refers to Feed Through

APPENDIX C SOFTWARE/HARDWARE REVISION (A)Effective2/97 Page C-3REVISION 1.21∗ Changed timing on Oil Return/Bypass solenoid from 10 seconds to 5 second

Seite 126 - HOSE PART NUMBERS

APPENDIX C SOFTWARE/HARDWARE REVISION (A)EffectivePage C-4 2/97REVISION CONTROLMINIMUM REWORK MINIMUM REVISION CURRENT REVISION7001-2185-01A F F7001-2

Seite 127 - 0301-0951-01

Effective2/97 Page D-1APPENDIX DINSTALLATION INSTRUCTIONSAppendix D is reserved for filing of Installation Instructions. When a kit is successfully i

Seite 128

APPENDIX D INSTALLATION INSTRUCTIONS (A)EffectivePage D-2 2/97

Seite 129

Effective2/97 Page iINTRODUCTIONGENERALThis service manual has four chapters covering the MRC-400/450 & ACT-4100/4500 Mobile Recycling Center,and

Seite 130

INTRODUCTION (B)EffectivePage ii 2/97FUNCTIONAL DESCRIPTION continue...Vacuum: After you open a vehicle air conditioning system, you can't immed

Seite 131

INTRODUCTION (B)Effective2/97 Page iiiREFRIGERANT SAFETY WARNINGS!USE STANDARD REFRIGERANT HANDLINGSAFETY PROCEDURES WHEN PERFORMING INSTALLATIONALWAY

Seite 132

TABLE OF CONTENTS FOR SERIAL AEffective2/97

Seite 133

INTRODUCTION (B)EffectivePage iv 2/97HANDLING MOS IC'S AND THEIR STATIC SENSITIVE DEVICESMost integrated circuits are high impedance devices. Th

Seite 134

INTRODUCTION (B)Effective2/97 Page v

Seite 135

TABLE OF CONTENTS FOR SERIAL BEffective2/97INTRODUCTIONGENERAL...

Seite 136 - T. WILSON

TABLE OF CONTENTS FOR SERIAL BEffective2/97CHAPTER 3 CHECKOUT-CALIBRATION-MAINTENANCE PROCEDURESCHECKOUT PROCEDURES ...

Seite 137

TABLE OF CONTENTS FOR SERIAL BEffective2/97REVISION CONTROL...

Seite 138 - CONFIGURATION

TABLE OF CONTENTS FOR SERIAL BEffective2/97

Seite 139 - APPENDIX A CONFIGURATION (B)

Effective2/97 Page 1-1CHAPTER 1AC/DC POWER DISTRIBUTIONAC/DC THEORY OF OPERATION!DANGEROUS HIGH VOLTAGESARE PRESENT IN THIS EQUIPMENTAlways use the &q

Seite 140 - BOARD CONFIGURATIONS

CHAPTER 1 AC/DC POWER DISTRIBUTION (B)EffectivePage 1-2 2/97DC DISTRIBUTIONPROCESSOR BOARDThe Processor Board has three bridge rectifiers and one 5 vo

Seite 141 - Page A-4 2/97

CHAPTER 1 AC/DC POWER DISTRIBUTION (B)Effective2/97 Page 1-3ALARMThe alarm is powered by the 24 volt DC voltage at J1 pin1. A beeper driver is used t

Seite 142 - ERROR CODES

CHAPTER 1 AC/DC POWER DISTRIBUTION (B)EffectivePage 1-4 2/97TROUBLESHOOTINGCOMPLAINT CORRECTIVE ACTIONI. Machine will not power up.Is the machine plug

Seite 143 - ERROR CODES 14 THROUGH 26

Effective2/97 Page 1-1CHAPTER 1AC/DC POWER DISTRIBUTIONAC/DC THEORY OF OPERATION!DANGEROUS HIGH VOLTAGESARE PRESENT IN THIS EQUIPMENTAlways use the &q

Seite 144 - ERROR CODES 27 THROUGH 30

SUN ELECTRIC CORPORATIONOne Sun ParkwayCrystal Lake, Illinois 60014 U.S.A.0695 REV A.PAGE:CHK BY:MODEL:DWG BY:TITLE:DWG:All information contained or d

Seite 145 - Page B-4 2/97

Effective12/98 Page 2-1CHAPTER 2THEORY OF OPERATION OPERATING MODES FOR SERIAL "B"POWER ON MODEThe Power On Mode is activated by turning on

Seite 146 - SOFTWARE/HARDWARE REVISION

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-2 12/98AUTO SEQUENCE MODEIn this Mode the MRC / ACT will automatically recover the system, recycle t

Seite 147 - REVISION 2.08

CHAPTER 2 THEORY OF OPERATION (B)Effective12/98 Page 2-3RECLAIM LOW, HIGH MODES continue...FIGURE 2-2 RECOVERY LOW, HIGH MODEThe Desiccant bag in the

Seite 148

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-4 12/98RECOVERY HOLD MODEIn Reclaim Hold the Condenser, Liquid and Zero solenoids are ON, allowing t

Seite 149 - HARDWARE REVISIONS

CHAPTER 2 THEORY OF OPERATION (B)Effective2/97 Page 2-5OIL RETURN MODEAs the compressor functions, small amounts of oil is carried off with the compr

Seite 150 - REVISION CONTROL

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-6 2/97PURGE MODEThe purpose of the Purge cycle is to remove non-condensables (Air) from the Recovery

Seite 151 - Page C-6 2/97

CHAPTER 2 THEORY OF OPERATION (B)Effective2/97 Page 2-7REFRIGERANT VAPOR PRESSURE CHARTR12 TEMPERATURE / PRESSURE CHARTUnit will purge down to Vapor

Seite 152 - INSTALLATION INSTRUCTIONS

CHAPTER 2 THEORY OF OPERATION (B)EffectivePage 2-8 2/97VACUUM MODEDuring this cycle the Vacuum, Crossover, Suction Separator, and Vent solenoids are

Seite 153 - Page D-2 2/97

CHAPTER 2 THEORY OF OPERATION (B)Effective2/97 Page 2-9OIL CHARGE MODEThe Liquid solenoid is CLOSED, the Oil and Crossover solenoids are OPENED and o